One or Two Family Home permitted ON or AFTER January 1, 2008 (Jan 1 2008-Feb 3, 2011)

 Smoke alarms are required as follows:

  • Minimum of One smoke alarm on every habitable level of the residence.
  • One smoke alarm at the base of each stairway.
  • One smoke alarm outside of each separate sleeping area. (Within 10 feet)
  • One smoke alarm inside every bedroom.
  • A minimum of one smoke alarm must be installed for every 1,200 square feet of living space per level.
  • Must be hardwired and interconnected smoke alarms with battery backup.
  • Must be Photoelectric type detector
  • Cannot be older than 10 years

Carbon monoxide alarms are required as follows:

Since March 31, 2006, carbon monoxide alarms have been required in all residences that have either: fossil fuel burning equipment or an attached enclosed garage. This law applied to all such residences whether or not the residence is being sold or transferred.

  • On every level of the residence, including habitable portions of basements and attics
  • Within 10 feet of each bedroom.
  • Combination alarms (photoelectric smoke and carbon monoxide alarm) may be used but must have voice activation.
  • Must be hardwired and interconnected with battery backup.
  • Follow the manufacturer’s instructions for placement.

Heat alarms are required as follows:

  • Must have a single heat alarm in any garage attached to or under the residence.
  • Must be hardwired and interconnected with or without battery backup to the existing smoke detection system.
  • Heat alarms are not required in garages of older homes unless renovation, addition or modification occurs after Jan. 1, 2008.

To Schedule a Smoke Detector Inspection:
Call Hanson Fire Headquarters the day you want the inspection done around 8am: (781)293-9571 to schedule a time that day. (We do not preschedule smoke detector inspections)
For more info on Scheduling/Requirements/Fees please click here to return to the previous page.